Part
Number
Maximum Rating (75°C) Specifications (25 °C)
Continuous Transient
Varistor
Voltage at
1mA Test
Current
Maximum
Clamping
Volt Vc at
200A Current
(8/20μs)
Typical
Capacitance
f = 1MHz
AC
Volts
DC
Volts
Energy
2ms
Peak
Surge
Current
8/20μs
Nominal
Discharge
Current
V
M(AC)
RMS
V
M(DC)
W
TM
I
TM
1 × Pulse
In
V
N(DC)
Min
V
N(DC)
Max Vc C
(V) (V) (J) (A) (A) (V) (V) (pF)
†
TCMOV34S111MP
115 150 280 50000 20000 163 202 305 115 0 0
†
TCMOV34S111NP
†
TCMOV34S111TP
†
TCMOV34S131MP
130 170 310 50000 20000 184 228 345 10000
†
TCMOV34S131NP
†
TCMOV34S131TP
†
TCMOV34S151MP
150 200 360 50000 20000 212 268 405 8000
†
TCMOV34S151NP
†
TCMOV34S151TP
†
TCMOV34S181MP
180 240 400 50000 20000 254 312 488 6800
†
TCMOV34S181NP
†
TCMOV34S181TP
†
TCMOV34S201MP
200 265 430 50000 20000 283 357 540 6500
†
TCMOV34S201NP
†
TCMOV34S201TP
†
TCMOV34S251MP
250 320 490 50000 20000 354 429 650 5000
†
TCMOV34S251NP
†
TCMOV34S251TP
†
TCMOV34S271MP
275 350 550 50000 20000 389 473 730 4500
†
TCMOV34S271NP
†
TCMOV34S271TP
†
TCMOV34S301MP
300 385 590 50000 20000 433 528 780 4050
†
TCMOV34S301NP
†
TCMOV34S301TP
†
TCMOV34S321MP
320 420 640 50000 20000 462 561 830 3800
†
TCMOV34S321NP
†
TCMOV34S321TP
TCMOV34S421MP
420 560 910 50000 20000 610 74 8 113 0 3000TCMOV34S421NP
TCMOV34S421TP
TCMOV34S461MP
460 610 960 50000 20000 642 783 118 8 2800TCMOV34S461NP
TCMOV34S461TP
TCMOV34S511MP
510 675 960 50000 20000 735 910 1350 2800TCMOV34S511NP
TCMOV34S511TP
TCMOV34S551MP
550 700 960 50000 20000 770 939 1415 2250TCMOV34S551NP
TCMOV34S551TP
TCMOV Series Ratings & Specifications
Notes:
1. Average Power dissipation of transients should not exceed 2.0 watts.
2.All34mmVaristorswithintheTCMOV34SSeriescanpass40kANon-repetitivePeakCurrentwithoutopeningofthermaldisconnect.
†DevicespassesNon-repetitivePeakCurrentsurgewithpossible,safeopeningofthermaldisconnect.
The same ratings and specifications apply to all devices whether with or without the monitored switch.
To order switch option desired, replace 'M'(WithMontitor-Bottom)with'T'(WithMonitor-Top)or'N'(WithoutMonitor)innexttolastdigitofpartnumber.
ForadditionalinformationpleaserefertothePartNumberingSystemsectionofthisdocument.