Pre-Engineered Solution Datasheet
Littelfuse.com © 2013 Littelfuse POWR-GARD
®
Products
Rev: 011113
1 of 3
LCP Fused Coordination PaneL
Selective Coordination Panel
Features/Benefits
• MeetsNEC
®
requirements
• ClassCCandJfuseholdershavebuilt-in
open-circuitindication
• Fast-actingULListedfusesprotectagainstshortcircuits
• Feedthrough/subfeedlugsand84-circuit
congurationavailable
• Groundandneutralbars
• Copperbusstandard
Advanced Design Options
• MLO,MainCircuitBreaker,orMainFusedPulloutdevice
• FusedClassTbranchcircuitpullout
• Sparefusecabinetaccessory(holdssixsparefuses)
• TVSSovervoltageprotection
• AnyNEMAenclosurerequired
• Highamperagesub-fedbranchbreakers(J60A)
• UniqueSpecierTool(seepg.146)toeasilyidentifypanel
congurationsfromtensofthousandsofoptions
Specifications
Voltage Ratings 120/208, 120/240, 277/480 VAC
Main Bus Rating 100 A - 400 A Standard
Conductor Terminals 6 AWG - 300 kcmil
UL Listed UL 67 Panel boards and UL 50 Enclosures
Web Resources
FuseCurves,samplerequests,downloadableCAD
drawingsandothertechnicalinformation:
Littelfuse.com/lcp
Description
TheLittelfuse
®
CoordinationPanelprovidesasimple,
time-savingsolutionforcircuitsthatrequireselective
coordination.ThisULListedproductsavestimeandmoney,
andincreasessafetybyminimizingsystemdowntime.
Applications
• Elevators
• Hospitals
• HotelandEntertainmentIndustry
• AmusementParksandStadiums
Code Requirements
SystemsrequiredbytheNEC
®
tobeselectively
coordinatedinclude:
• HealthCareEssentialElectricalSystems(NEC517.26)
• Elevators(NEC620.62)
• EmergencySystems(NEC700.27)
• LegallyRequiredStandbySystems(NEC
701.18)
• CriticalOperationsPowerSystems(NEC708.54)
†
Fuses quoted separately to meet panel specifications. Coordination for breakers >60 A depends on upstream and
downstream devices. More specialized configurations are also available. Contact factory for more information.
Note: The Littelfuse LPS, LPMP and LCP products are custom
designed products that fall outside standard specifications.
Custom Options (select one from each column)
number
oF
CirCuits
VoLtage main deViCes
neutraL
rating
PaneL
mounting
PaneL
door
Fuse
HoLders
branCH CirCuit
ProteCtion deViCes
(1-3 PoLe)
†
PaneL
Feed
oPtionaL Lugs
standard
enCLosure
rating
2 - 42
120/208 V 3P, 4 W
120/240 V 1P, 3 W
277/480 V 3P, 4 W
125, 225, 400 or
600 A MLO
Up to 600 A MCB
or Main Fuse
Pullout
100%
200%
Surface
Flush
Standard
Door-in-door
30 A Class CC
60 A Class J
10 A- 60 A fused
circuit breaker
60 A-200 A
fused pullouts
Sub-fed circuit breakers
>60 A
(not fused)
Top
Bottom
None
Sub-Fed (MLO panels)
Feed-Through
NEMA 1
NEMA 3R
NEMA 4X
ToquicklyspecifytheLCPpanel,
visit
Littelfuse.com/lcp
anddownloadtheSpecierTool.